NA2XY Cable

0,6/1 kV NA2XY Cable

0.6/1 kV NA2XY CableApplicationThese power cables are used for electricity supply in low voltage installation systems. They are well adapted to underground use

0.6/1 kV NA2XY Cable

Application

These power cables are used for electricity supply in low voltage installation systems. They are well adapted to underground use in industrial applications with an additional mechanical protection. These cables can be fixed on cable trays, within conduits or fixed to walls.

Standard and Approval

VDE 0276 part 603
IEC 60502
IEC 60228


Construction

 


Cable Parameter

0.6/1kV-1 Core Aluminum Conductor XLPE Insulated PVC Sheathed Power Cable
No. of cores and nominal cross section Thickness of Insulation Thickness of Sheath Approx. overall Diameter Approx. weight Max. DC resistance of conductor(20℃) Current carrying capacity
(mm2) (mm) (mm) (mm) (kg/km) (Ω/km) In Air(A) In Ground(A)
1X10 0.7 1.4 8.0 75 3.08 55 71
1X16 0.7 1.4 9.0 106 1.91 71 91
1X25 0.9 1.4 10.6 150 1.20 94 115
1X35 0.9 1.4 11.6 180 0.868 115 140
1X50 1.0 1.4 13.1 240 0.641 140 165
1X70 1.1 1.4 15.0 320 0.443 180 205
1X95 1.1 1.5 16.8 400 0.320 220 245
1X120 1.2 1.5 18.4 500 0.253 260 280
1X150 1.4 1.6 20.5 600 0.206 300 315
1X185 1.6 1.6 22.6 730 0.164 350 360
1X240 1.7 1.7 25.2 930 0.125 414 420
1x300 1.8 1.8 27.8 1140 0.100 485 475
1x400 2.0 1.9 31.4 1500 0.0778 570 545
1x500 2.2 2.0 34.9 1800 0.0605 670 620
1X630 2.4 2.2 39.1 2285 0.0469 790 705

0.6/1kV-2 Core Aluminum Conductor XLPE Insulated PVC Sheathed Power Cable
No. of cores and nominal cross section Thickness of Insulation Thickness of Sheath Approx. overall Diameter Approx. weight Max. DC resistance of conductor(20℃) Current carrying capacity
(mm2) (mm) (mm) (mm) (kg/km) (Ω/km) In Air(A) In Ground(A)
2X10 0.7 1.8 15.4 200 3.08 58 78
2X16 0.7 1.8 17.4 270 1.91 75 100
2X25 0.9 1.8 20.5 380 1.20 100 130
2X35 0.9 1.8 22.5 480 0.868 120 155
2X50 1.0 1.8 20.3 490 0.641 150 185
2X70 1.1 1.8 23.3 630 0.443 190 225
2X95 1.1 1.9 26.2 820 0.320 235 275
2X120 1.2 2.0 29.4 1000 0.253 275 315
2X150 1.4 2.2 32.6 1250 0.206 315 350
2X185 1.6 2.3 36.0 1540 0.164 365 395

0.6/1kV-3 Core Aluminum Conductor XLPE Insulated PVC Sheathed Power Cable
No. of cores and nominal cross section Thickness of Insulation Thickness of Sheath Approx. overall Diameter Approx. weight Max. DC resistance of conductor(20℃) Current carrying capacity
(mm2) (mm) (mm) (mm) (kg/km) (Ω/km) In Air(A) In Ground(A)
3X10 0.7 1.8 17.2 250 3.08 50 66
3X16 0.7 1.8 19.4 330 1.91 65 85
3X25 0.9 1.8 22.8 480 1.20 87 110
3X35 0.9 1.8 25.0 580 0.868 105 130
3X50 1.0 1.8 24.4 670 0.641 130 160
3X70 1.1 1.9 29.4 910 0.443 165 195
3X95 1.1 2.0 33.6 1170 0.320 205 235
3X120 1.2 2.1 35.9 1460 0.253 240 265
3X150 1.4 2.3 39.9 1820 0.206 270 300
3X185 1.6 2.4 44.1 2200 0.164 315 340
3X240 1.7 2.6 51.1 2850 0.125 375 395
3X300 1.8 2.7 56.1 3500 0.100 435 445
3X400 2.0 3.0 62.4 4500 0.0778 510 510

0.6/1kV-4 Core Aluminum Conductor XLPE Insulated PVC Sheathed Power Cable
No. of cores and nominal cross section Thickness of Insulation Thickness of Sheath Approx. overall Diameter Approx. weight Max. DC resistance of conductor(20℃) Current carrying capacity
(mm2) (mm) (mm) (mm) (kg/km) (Ω/km) In Air(A) In Ground(A)
4X10 0.7 1.8 18.6 300 3.08 50 66
4X16 0.7 1.8 21.0 400 1.91 65 85
4X25 0.9 1.8 24.9 570 1.20 87 110
4X35 0.9 1.8 28.3 710 0.868 105 130
4X50 1.0 1.8 28.4 850 0.641 130 160
4X70 1.1 2.0 33.1 1160 0.443 165 195
4X95 1.1 2.1 37.1 1520 0.320 205 235
4X120 1.2 2.2 40.8 1898 0.253 240 265
4X150 1.4 2.4 45.2 2369 0.206 270 300
4X185 1.6 2.6 52.1 2925 0.164 315 340
4X240 1.7 2.8 57.8 3700 0.125 375 395
4X300 1.8 3.0 63.5 4580 0.100 435 445
4X400 2.0 3.3 70.9 5800 0.0778 510 510

0.6/1kV-5 Core Aluminum Conductor XLPE Insulated PVC Sheathed Power Cable
No. of cores and nominal cross section Thickness of Insulation Thickness of Sheath Approx. overall Diameter Approx. weight Max. DC resistance of conductor(20℃) Current carrying capacity
(mm2) (mm) (mm) (mm) (kg/km) (Ω/km) In Air(A) In Ground(A)
5X10 0.7 1.8 18.8 360 3.08 50 66
5X16 0.7 1.8 21.8 485 1.91 65 85
5X25 0.9 1.8 26.2 690 1.20 87 110
5X35 0.9 1.8 28.0 865 0.868 105 130
5X50 1.0 1.9 32.4 1138 0.641 130 160
5X70 1.1 2.1 37.4 1575 0.443 165 195
5X95 1.1 2.2 41.7 2068 0.320 205 235
5X120 1.2 2.4 46.2 2550 0.253 240 265
5X150 1.4 2.6 53.1 3165 0.206 270 300
5X185 1.6 2.8 58.9 3950 0.164 315 340
5X240 1.7 3.0 65.6 5025 0.125 375 395
5X300 1.8 3.2 72.0 6190 0.100 435 445

0.6/1kV-3+1 Core Aluminum Conductor XLPE Insulated PVC Sheathed Power Cable
No. of cores and nominal cross section Thickness of Insulation Thickness of Sheath Approx. overall Diameter Approx. weight Max. DC resistance of conductor(20℃) Current carrying capacity
(mm2) (mm) (mm) (mm) (kg/km) (Ω/km) In Air(A) In Ground(A)
3X16+1X10 0.7/0.7 1.8 19.4 370 1.91/3.08 65 85
3X25+1X16 0.9/0.7 1.8 22.8 520 1.20/1.91 87 110
3X35+1X16 0.9/0.7 1.8 25.1 650 0.868/1.91 105 130
3X50+1X25 1.0/0.9 1.8 28.2 780 0.641/1.20 130 160
3X70+1X35 1.1/0.9 1.9 31.9 1050 0.443/0.868 165 195
3X95+1X50 1.1/1.0 2.1 35.7 1460 0.320/0.641 205 235
3X120+1X70 1.2/1.1 2.2 39.6 1820 0.253/0.443 240 265
3X150+1X70 1.4/1.1 2.3 43.6 2150 0.206/0.443 270 300
3X185+1X95 1.6/1.1 2.5 49.8 2725 0.164/0.320 315 340
3X240+1X120 1.7/1.2 2.7 55.3 3480 0.125/0.253 375 395
3X300+1X150 1.8/1.4 2.9 57.0 4230 0.100/0.206 435 445
3X400+1X185 2.0/1.7 3.1 70.0 5520 0.0778/0.164 510 510

0.6/1kV-4+1core Aluminum Conductor XLPE Insulated PVC Sheathed Power Cable
No. of cores and nominal cross section Thickness of Insulation Thickness of Sheath Approx. overall Diameter Approx. weight Max. DC resistance of conductor(20℃) Current carrying capacity
(mm2) (mm) (mm) (mm) (kg/km) (Ω/km) In Air(A) In Ground(A)
4X16+1X10 0.7/0.7 1.8 21.3 450 1.91/3.08 65 85
4X25+1X16 0.9/0.7 1.8 25.7 650 1.20/1.91 87 110
4X35+1X16 0.9/0.7 1.8 28.2 795 0.868/1.91 105 130
4X50+1X25 1.0/0.9 1.9 28.9 1020 0.641/1.20 130 160
4X70+1X35 1.1/0.9 2.0 32.2 1360 0.443/0.868 165 195
4X95+1X50 1.1/1.0 2.2 36.9 1870 0.320/0.641 205 235
4X120+1X70 1.2/1.1 2.3 40.8 2342 0.253/0.443 240 265
4X150+1X70 1.4/1.1 2.5 44.7 2778 0.206/0.443 270 300
4X185+1X95 1.6/1.1 2.7 50.7 3495 0.164/0.320 315 340
4X240+1X120 1.7/1.2 2.9 56.4 4416 0.125/0.253 375 395
4X300+1X150 1.8/1.4 3.1 64.0 5422 0.100/0.206 435 445

0.6/1kV-3+2 Core Aluminum Conductor XLPE Insulated PVC Sheathed Power Cable
No. of cores and nominal cross section Thickness of Insulation Thickness of Sheath Approx. overall Diameter Approx. weight Max. DC resistance of conductor(20℃) Current carrying capacity
(mm2) (mm) (mm) (mm) (kg/km) (Ω/km) In Air(A) In Ground(A)
3X16+2X10 0.7/0.7 1.8 20.8 425 1.91/3.08 65 85
3X25+2X16 0.9/0.7 1.8 25.2 600 1.20/1.91 87 110
3X35+2X16 0.9/0.7 1.8 26.8 720 0.868/1.91 105 130
3X50+2X25 1.0/0.9 1.9 28.7 955 0.641/1.20 130 160
3X70+2X35 1.1/0.9 2.0 33.7 1230 0.443/0.868 165 195
3X95+2X50 1.1/1.0 2.2 38.3 1706 0.320/0.641 205 235
3X120+2X70 1.2/1.1 2.3 43.2 2180 0.253/0.443 240 265
3X150+2X70 1.4/1.1 2.4 46.5 2525 0.206/0.443 270 300
3X185+2X95 1.6/1.1 2.6 51.9 3195 0.164/0.320 315 340
3X240+2X120 1.7/1.2 2.8 58.0 4050 0.125/0.253 375 395
3X300+2X150 1.8/1.4 3.0 64.2 4983 0.100/0.206 435 445

Contact Us, Now.
24-hour service hotline
Contact online customer service
Add: Factory :No.33 Zhengzhou City, Henan Province,China
Related products
Aluminum medium voltage power cables
Aluminum medium voltage power cables
Underground Twisted Cable
Underground Twisted Cable
15-35KV MV-105 EPR/PVC Copper Tape Shield cable
Copper Single Conductor 15-35KV MV-105 EPR/PVC Copper Tape Shield cable
0.6/1 kV NYCY PVC insulated power cables
0.6/1 kV NYCY PVC insulated power cables