0.6/1 kV NA2XY Cable
Application
These power cables are used for electricity supply in low voltage installation systems. They are well adapted to underground use in industrial applications with an additional mechanical protection. These cables can be fixed on cable trays, within conduits or fixed to walls.Standard and Approval
VDE 0276 part 603IEC 60502
IEC 60228
Construction
Cable Parameter
0.6/1kV-1 Core Aluminum Conductor XLPE Insulated PVC Sheathed Power Cable| No. of cores and nominal cross section | Thickness of Insulation | Thickness of Sheath | Approx. overall Diameter | Approx. weight | Max. DC resistance of conductor(20℃) | Current carrying capacity | |
| (mm2) | (mm) | (mm) | (mm) | (kg/km) | (Ω/km) | In Air(A) | In Ground(A) |
| 1X10 | 0.7 | 1.4 | 8.0 | 75 | 3.08 | 55 | 71 |
| 1X16 | 0.7 | 1.4 | 9.0 | 106 | 1.91 | 71 | 91 |
| 1X25 | 0.9 | 1.4 | 10.6 | 150 | 1.20 | 94 | 115 |
| 1X35 | 0.9 | 1.4 | 11.6 | 180 | 0.868 | 115 | 140 |
| 1X50 | 1.0 | 1.4 | 13.1 | 240 | 0.641 | 140 | 165 |
| 1X70 | 1.1 | 1.4 | 15.0 | 320 | 0.443 | 180 | 205 |
| 1X95 | 1.1 | 1.5 | 16.8 | 400 | 0.320 | 220 | 245 |
| 1X120 | 1.2 | 1.5 | 18.4 | 500 | 0.253 | 260 | 280 |
| 1X150 | 1.4 | 1.6 | 20.5 | 600 | 0.206 | 300 | 315 |
| 1X185 | 1.6 | 1.6 | 22.6 | 730 | 0.164 | 350 | 360 |
| 1X240 | 1.7 | 1.7 | 25.2 | 930 | 0.125 | 414 | 420 |
| 1x300 | 1.8 | 1.8 | 27.8 | 1140 | 0.100 | 485 | 475 |
| 1x400 | 2.0 | 1.9 | 31.4 | 1500 | 0.0778 | 570 | 545 |
| 1x500 | 2.2 | 2.0 | 34.9 | 1800 | 0.0605 | 670 | 620 |
| 1X630 | 2.4 | 2.2 | 39.1 | 2285 | 0.0469 | 790 | 705 |
0.6/1kV-2 Core Aluminum Conductor XLPE Insulated PVC Sheathed Power Cable
| No. of cores and nominal cross section | Thickness of Insulation | Thickness of Sheath | Approx. overall Diameter | Approx. weight | Max. DC resistance of conductor(20℃) | Current carrying capacity | |
| (mm2) | (mm) | (mm) | (mm) | (kg/km) | (Ω/km) | In Air(A) | In Ground(A) |
| 2X10 | 0.7 | 1.8 | 15.4 | 200 | 3.08 | 58 | 78 |
| 2X16 | 0.7 | 1.8 | 17.4 | 270 | 1.91 | 75 | 100 |
| 2X25 | 0.9 | 1.8 | 20.5 | 380 | 1.20 | 100 | 130 |
| 2X35 | 0.9 | 1.8 | 22.5 | 480 | 0.868 | 120 | 155 |
| 2X50 | 1.0 | 1.8 | 20.3 | 490 | 0.641 | 150 | 185 |
| 2X70 | 1.1 | 1.8 | 23.3 | 630 | 0.443 | 190 | 225 |
| 2X95 | 1.1 | 1.9 | 26.2 | 820 | 0.320 | 235 | 275 |
| 2X120 | 1.2 | 2.0 | 29.4 | 1000 | 0.253 | 275 | 315 |
| 2X150 | 1.4 | 2.2 | 32.6 | 1250 | 0.206 | 315 | 350 |
| 2X185 | 1.6 | 2.3 | 36.0 | 1540 | 0.164 | 365 | 395 |
0.6/1kV-3 Core Aluminum Conductor XLPE Insulated PVC Sheathed Power Cable
| No. of cores and nominal cross section | Thickness of Insulation | Thickness of Sheath | Approx. overall Diameter | Approx. weight | Max. DC resistance of conductor(20℃) | Current carrying capacity | |
| (mm2) | (mm) | (mm) | (mm) | (kg/km) | (Ω/km) | In Air(A) | In Ground(A) |
| 3X10 | 0.7 | 1.8 | 17.2 | 250 | 3.08 | 50 | 66 |
| 3X16 | 0.7 | 1.8 | 19.4 | 330 | 1.91 | 65 | 85 |
| 3X25 | 0.9 | 1.8 | 22.8 | 480 | 1.20 | 87 | 110 |
| 3X35 | 0.9 | 1.8 | 25.0 | 580 | 0.868 | 105 | 130 |
| 3X50 | 1.0 | 1.8 | 24.4 | 670 | 0.641 | 130 | 160 |
| 3X70 | 1.1 | 1.9 | 29.4 | 910 | 0.443 | 165 | 195 |
| 3X95 | 1.1 | 2.0 | 33.6 | 1170 | 0.320 | 205 | 235 |
| 3X120 | 1.2 | 2.1 | 35.9 | 1460 | 0.253 | 240 | 265 |
| 3X150 | 1.4 | 2.3 | 39.9 | 1820 | 0.206 | 270 | 300 |
| 3X185 | 1.6 | 2.4 | 44.1 | 2200 | 0.164 | 315 | 340 |
| 3X240 | 1.7 | 2.6 | 51.1 | 2850 | 0.125 | 375 | 395 |
| 3X300 | 1.8 | 2.7 | 56.1 | 3500 | 0.100 | 435 | 445 |
| 3X400 | 2.0 | 3.0 | 62.4 | 4500 | 0.0778 | 510 | 510 |
0.6/1kV-4 Core Aluminum Conductor XLPE Insulated PVC Sheathed Power Cable
| No. of cores and nominal cross section | Thickness of Insulation | Thickness of Sheath | Approx. overall Diameter | Approx. weight | Max. DC resistance of conductor(20℃) | Current carrying capacity | |
| (mm2) | (mm) | (mm) | (mm) | (kg/km) | (Ω/km) | In Air(A) | In Ground(A) |
| 4X10 | 0.7 | 1.8 | 18.6 | 300 | 3.08 | 50 | 66 |
| 4X16 | 0.7 | 1.8 | 21.0 | 400 | 1.91 | 65 | 85 |
| 4X25 | 0.9 | 1.8 | 24.9 | 570 | 1.20 | 87 | 110 |
| 4X35 | 0.9 | 1.8 | 28.3 | 710 | 0.868 | 105 | 130 |
| 4X50 | 1.0 | 1.8 | 28.4 | 850 | 0.641 | 130 | 160 |
| 4X70 | 1.1 | 2.0 | 33.1 | 1160 | 0.443 | 165 | 195 |
| 4X95 | 1.1 | 2.1 | 37.1 | 1520 | 0.320 | 205 | 235 |
| 4X120 | 1.2 | 2.2 | 40.8 | 1898 | 0.253 | 240 | 265 |
| 4X150 | 1.4 | 2.4 | 45.2 | 2369 | 0.206 | 270 | 300 |
| 4X185 | 1.6 | 2.6 | 52.1 | 2925 | 0.164 | 315 | 340 |
| 4X240 | 1.7 | 2.8 | 57.8 | 3700 | 0.125 | 375 | 395 |
| 4X300 | 1.8 | 3.0 | 63.5 | 4580 | 0.100 | 435 | 445 |
| 4X400 | 2.0 | 3.3 | 70.9 | 5800 | 0.0778 | 510 | 510 |
0.6/1kV-5 Core Aluminum Conductor XLPE Insulated PVC Sheathed Power Cable
| No. of cores and nominal cross section | Thickness of Insulation | Thickness of Sheath | Approx. overall Diameter | Approx. weight | Max. DC resistance of conductor(20℃) | Current carrying capacity | |
| (mm2) | (mm) | (mm) | (mm) | (kg/km) | (Ω/km) | In Air(A) | In Ground(A) |
| 5X10 | 0.7 | 1.8 | 18.8 | 360 | 3.08 | 50 | 66 |
| 5X16 | 0.7 | 1.8 | 21.8 | 485 | 1.91 | 65 | 85 |
| 5X25 | 0.9 | 1.8 | 26.2 | 690 | 1.20 | 87 | 110 |
| 5X35 | 0.9 | 1.8 | 28.0 | 865 | 0.868 | 105 | 130 |
| 5X50 | 1.0 | 1.9 | 32.4 | 1138 | 0.641 | 130 | 160 |
| 5X70 | 1.1 | 2.1 | 37.4 | 1575 | 0.443 | 165 | 195 |
| 5X95 | 1.1 | 2.2 | 41.7 | 2068 | 0.320 | 205 | 235 |
| 5X120 | 1.2 | 2.4 | 46.2 | 2550 | 0.253 | 240 | 265 |
| 5X150 | 1.4 | 2.6 | 53.1 | 3165 | 0.206 | 270 | 300 |
| 5X185 | 1.6 | 2.8 | 58.9 | 3950 | 0.164 | 315 | 340 |
| 5X240 | 1.7 | 3.0 | 65.6 | 5025 | 0.125 | 375 | 395 |
| 5X300 | 1.8 | 3.2 | 72.0 | 6190 | 0.100 | 435 | 445 |
0.6/1kV-3+1 Core Aluminum Conductor XLPE Insulated PVC Sheathed Power Cable
| No. of cores and nominal cross section | Thickness of Insulation | Thickness of Sheath | Approx. overall Diameter | Approx. weight | Max. DC resistance of conductor(20℃) | Current carrying capacity | |
| (mm2) | (mm) | (mm) | (mm) | (kg/km) | (Ω/km) | In Air(A) | In Ground(A) |
| 3X16+1X10 | 0.7/0.7 | 1.8 | 19.4 | 370 | 1.91/3.08 | 65 | 85 |
| 3X25+1X16 | 0.9/0.7 | 1.8 | 22.8 | 520 | 1.20/1.91 | 87 | 110 |
| 3X35+1X16 | 0.9/0.7 | 1.8 | 25.1 | 650 | 0.868/1.91 | 105 | 130 |
| 3X50+1X25 | 1.0/0.9 | 1.8 | 28.2 | 780 | 0.641/1.20 | 130 | 160 |
| 3X70+1X35 | 1.1/0.9 | 1.9 | 31.9 | 1050 | 0.443/0.868 | 165 | 195 |
| 3X95+1X50 | 1.1/1.0 | 2.1 | 35.7 | 1460 | 0.320/0.641 | 205 | 235 |
| 3X120+1X70 | 1.2/1.1 | 2.2 | 39.6 | 1820 | 0.253/0.443 | 240 | 265 |
| 3X150+1X70 | 1.4/1.1 | 2.3 | 43.6 | 2150 | 0.206/0.443 | 270 | 300 |
| 3X185+1X95 | 1.6/1.1 | 2.5 | 49.8 | 2725 | 0.164/0.320 | 315 | 340 |
| 3X240+1X120 | 1.7/1.2 | 2.7 | 55.3 | 3480 | 0.125/0.253 | 375 | 395 |
| 3X300+1X150 | 1.8/1.4 | 2.9 | 57.0 | 4230 | 0.100/0.206 | 435 | 445 |
| 3X400+1X185 | 2.0/1.7 | 3.1 | 70.0 | 5520 | 0.0778/0.164 | 510 | 510 |
0.6/1kV-4+1core Aluminum Conductor XLPE Insulated PVC Sheathed Power Cable
| No. of cores and nominal cross section | Thickness of Insulation | Thickness of Sheath | Approx. overall Diameter | Approx. weight | Max. DC resistance of conductor(20℃) | Current carrying capacity | |
| (mm2) | (mm) | (mm) | (mm) | (kg/km) | (Ω/km) | In Air(A) | In Ground(A) |
| 4X16+1X10 | 0.7/0.7 | 1.8 | 21.3 | 450 | 1.91/3.08 | 65 | 85 |
| 4X25+1X16 | 0.9/0.7 | 1.8 | 25.7 | 650 | 1.20/1.91 | 87 | 110 |
| 4X35+1X16 | 0.9/0.7 | 1.8 | 28.2 | 795 | 0.868/1.91 | 105 | 130 |
| 4X50+1X25 | 1.0/0.9 | 1.9 | 28.9 | 1020 | 0.641/1.20 | 130 | 160 |
| 4X70+1X35 | 1.1/0.9 | 2.0 | 32.2 | 1360 | 0.443/0.868 | 165 | 195 |
| 4X95+1X50 | 1.1/1.0 | 2.2 | 36.9 | 1870 | 0.320/0.641 | 205 | 235 |
| 4X120+1X70 | 1.2/1.1 | 2.3 | 40.8 | 2342 | 0.253/0.443 | 240 | 265 |
| 4X150+1X70 | 1.4/1.1 | 2.5 | 44.7 | 2778 | 0.206/0.443 | 270 | 300 |
| 4X185+1X95 | 1.6/1.1 | 2.7 | 50.7 | 3495 | 0.164/0.320 | 315 | 340 |
| 4X240+1X120 | 1.7/1.2 | 2.9 | 56.4 | 4416 | 0.125/0.253 | 375 | 395 |
| 4X300+1X150 | 1.8/1.4 | 3.1 | 64.0 | 5422 | 0.100/0.206 | 435 | 445 |
0.6/1kV-3+2 Core Aluminum Conductor XLPE Insulated PVC Sheathed Power Cable
| No. of cores and nominal cross section | Thickness of Insulation | Thickness of Sheath | Approx. overall Diameter | Approx. weight | Max. DC resistance of conductor(20℃) | Current carrying capacity | |
| (mm2) | (mm) | (mm) | (mm) | (kg/km) | (Ω/km) | In Air(A) | In Ground(A) |
| 3X16+2X10 | 0.7/0.7 | 1.8 | 20.8 | 425 | 1.91/3.08 | 65 | 85 |
| 3X25+2X16 | 0.9/0.7 | 1.8 | 25.2 | 600 | 1.20/1.91 | 87 | 110 |
| 3X35+2X16 | 0.9/0.7 | 1.8 | 26.8 | 720 | 0.868/1.91 | 105 | 130 |
| 3X50+2X25 | 1.0/0.9 | 1.9 | 28.7 | 955 | 0.641/1.20 | 130 | 160 |
| 3X70+2X35 | 1.1/0.9 | 2.0 | 33.7 | 1230 | 0.443/0.868 | 165 | 195 |
| 3X95+2X50 | 1.1/1.0 | 2.2 | 38.3 | 1706 | 0.320/0.641 | 205 | 235 |
| 3X120+2X70 | 1.2/1.1 | 2.3 | 43.2 | 2180 | 0.253/0.443 | 240 | 265 |
| 3X150+2X70 | 1.4/1.1 | 2.4 | 46.5 | 2525 | 0.206/0.443 | 270 | 300 |
| 3X185+2X95 | 1.6/1.1 | 2.6 | 51.9 | 3195 | 0.164/0.320 | 315 | 340 |
| 3X240+2X120 | 1.7/1.2 | 2.8 | 58.0 | 4050 | 0.125/0.253 | 375 | 395 |
| 3X300+2X150 | 1.8/1.4 | 3.0 | 64.2 | 4983 | 0.100/0.206 | 435 | 445 |